HOME    New Energy    Energy Storage Safety Monitoring    Energy storage safety modules for thermal runaway detection (CO+H2+smoke+temperature)

Energy storage safety modules for thermal runaway detection (CO+H2+smoke+temperature)

PN: BSM-1004MB   
All in one Energy storage safety modules (CO+ H2+ smoke +temperature)
  •  

    Energy storage safety modules for thermal runaway detection

    (CO+ H2 + smoke +temperature)

     

    1. Introduction

    The 4 in 1 Energy storage safety modules integrated with carbon monoxide, hydrogen, smoke and temperature sensors. Which is an integrated module of semiconductor metal oxide gas sensor and optical smoke sensor based on Rainbow's MEMS technology.

    This product is an early warning device for lithium battery thermal runaway fire and an emergency alarm device during the fire. Detection and alarm in energy storage applications and security detection.
    The module can detect carbon monoxide, hydrogen, smoke and temperature in a complex environment in real time. High and low limit alarms can be set according to the concentration values. The sensor of this series of modules is a multi-channel array gas sensor composed of different material systems, using specific conditioning circuits and precise intelligent algorithms to determine the warning level of various dangerous gas concentrations in the current environment.

     
    2. Feature
    BSM-1004MB series module can identify and detect the dangerous gas concentration content, smoke concentration content and temperature data, the module has the characteristics of high sensitivity, high resolution, low power consumption, long service life, can provide RS485, CAN, analog voltage signal, PWM signal and other output mode, has high stability, excellent anti-interference ability, temperature compensation, excellent linear output.
     
    3. Application
     Energy storage safety detection, which can be used to monitor the battery pack parameters
     Thermal runaway safety early warning and monitoring of lithium-ion batteries
     Energy storage power station safety early warning and monitoring
     
    4. Parameters
    4.1

    Product Name

    Li-battery Thermal Runaway Sensor

    Model

    BSM-1004

    Detect Gas

    Temperature

    VOC

    CO

    H2

    Range

    -40-125℃

    0.1-1000ppm

    1-1000ppm

    1-1000ppm

    Extended concentration

    -45-130℃

    5000ppm

    20000ppm

    20000ppm

    Resolution

    0.02℃

    <0.5ppm

    <10ppm

    <1ppm

    Response time

    <2s

    <10s

    <10s

    <10s

    Recovery time

    <2s

    <30s

    <30s

    <30s

    Measuring principle

    Capacitive

    MOS Semiconductor

    MOS Semiconductor

    MOS semiconductor

    Supply voltage

    24V DC (with reverse connection protection)

    Output signal

    RS485/PWM

    Working temperature

    -40~85

    Working humidity

    10-95% RH (no condensation)

    Storage temperature

    -40-85℃

    Storage humidity

    < 75% RH

    Power consumption

    <1.0W

    Module size

    75*55*30mm(L*W*H)

    Lifetime

    > 10 Years

     
    4.2 Dimensions
     
    4.3 Definition of pin
    Note: It is pin 1-5 from left to right.